Estimation of central air conditioning water pipe diameter

Selection of condensate pipe: Generally, the nominal diameter of the condensate pipe can be approximately selected based on the cooling load Q (kW) of the unit according to the following data.

The relationship between pipe diameter and load

load

Diameter of condensate pipe

load

Diameter of condensate pipe

Q≤7KW

DN20mm

Q=7.1~17.6kW

DN25mm

Q=17.7~100kW

DN32mm

Q=101~176kW

DN40mm

Q=177~598kW

DN50mm

Q=599~1055kW

DN80mm

The condensed water generated during the operation of fan coil units, integral air conditioners, and modular air conditioning units must be promptly discharged.

The design of condensate discharge pipelines should pay attention to the following matters:

Horizontal pipelines should maintain a slope of no less than 0.3% along the direction of water flow; And no areas with accumulated water are allowed. When using polyvinyl chloride plastic pipes, it is generally not necessary to perform insulation and vapor barrier treatment to prevent condensation. When using galvanized steel pipes, insulation layers should usually be installed.

The relationship between cooling capacity and pipe diameter (estimated)

cold water system

cold water system

Total cooling capacity Q (kw)

Pipe diameter (mm)

Total cooling capacity Q (kw)

Pipe diameter (mm)

5.5-10kw

25

210-410kw

100

10-30kw

32

410-750kw

125

30-40kw

40

750-1200kw

150

40-65k

50

1200-2500kw

200

65-120kw

65

Greater than 2500kw

250

120-210kw