Description: 3321/3331 American JENCO conductivity and resistivity control/transmitter standard 1/8DIN design correction value power-off memory function with LCD backlight display 4-20mA isolation current output (3331) two groups (conductivity and resistivity) electrical control (3321) automatic/manual temperature compensation function
Product Details

3321/3331 American JENCO conductivity and resistivity control/transmitter

  • Standard 1/8DIN design calibration value power-off memory function
  • Equipped with LCD backlight display
  • 4~20mA isolated current output (3331)
  • Two groups (conductivity, resistivity) electrical control (3321)
  • Automatic/manual temperature compensation function
  • CE certification

    specifications

  • conductivity measuring range 0.000uS/cm~19.99mS/cm
    resolution 0.001uS/cm
    accuracy 0.5% ± 1 word
    resistivity measuring range 0.50~19.99MΩ
    resolution 0.01MΩ
    accuracy 0.5% ± 1 word
    temperature range -10~120.0℃
    resolution 0.1℃
    accuracy ±0.3℃
    Types of electrode constants 0.01, 0.1, 1.0 (2-wire conductive electrode)
    reference temperature 25.0 ℃, factory setting
    Relay control output/ZUI high load Two sets of ON/OFF relays control/115VAC or 2./220VAC (3321) within the system
    current output A set of isolated 4-20mA analog outputs (3331 type)
    Input impedance >1012Ω
    External dimensions 1/4DIN standard body, 96x48x110mm
    Dimension 92x45mm
    power supply 100~240VAC,50/60Hz

    optional accessories

    model brief introduction
    Conductivity electrode 392-122 Pure water and ultra pure water treatment field (can be used for a long time below 80 ℃)
    392-126 Pure water and ultra pure water treatment field (can be used for a long time below 80 ℃)
    392-125 In the field of circulating water and ordinary water treatment (can be used for a long time below 80 ℃)
    EC621-001 Pure water and ultra pure water treatment field (can be used for a long time below 120 ℃)
    EC621-01 Pure water and ultra pure water treatment field (can be used for a long time below 120 ℃)
    sealed box 011-150-00 Dial type installation