Application field
Water treatment plant: turbidity monitoring of pre filtration, post filtration, sedimentation, and effluent water; Monitoring the water quality of municipal sewage. Industrial process water quality monitoring, circulating cooling water, activated carbon filter effluent, membrane filtration effluent, etc
Technical Characteristics
Imported chips from Germany, highly integrated circuit boards
※ Easy to operate, low maintenance required
Ultra bright and stable pure white light source, with a lifespan 100 times longer than ordinary light sources
Stainless steel inner liner and shell/anti fog lens/dual light path compensation/automatic defoaming design
※ Applied to water treatment automation work, LCD display is clear
Technical instructions
Measurement principle: principles of transmitted light and scattered light
Range 0-20NTU 0-200NTU; 0-2000NTU; 0-5000NTU
Accuracy<FS (full scale) ± 1%, ± 5%
Reproducibility<FS ± 1%
Resolution of 0.01NTU/0.1NTU
Drift per hour<0.1NTU
Response time 10 seconds
Analog output isolated 4-20mA current output
Relay output high and low points, hysteresis can be set by any program
On site display LCD widescreen display
Analog output 4-20mA, maximum load 750 Ω
Switch output 2 relays, 220AVC/5A
Dimensions 231x208x110 mmWall mounted instrument
Power supply AC220V ± 10% (standard), 24VDC/15W
Sensor parameters:
Material: 316 stainless steel (standard) PVC
Connection process: G1 thread (submerged) quick interface (flow-through)
Cable length:10m(Optional)
Medium temperature: Sensor: -20~60℃
Process pressure: 3bar
Protection level: IP68 (submerged installation)