E-mail
2011790575@sina.com
-
Phone
15756660791
-
Address
Xi'an
Sichuan Shuchen Electrical Equipment Co., Ltd
2011790575@sina.com
15756660791
Xi'an
35KV outdoor column mounted intelligent watchdog with isolated vacuum circuit breakerUsed for exchanging 50HZ three-phase power systems, as a means of dividing and combining load currents, overload currents, and short-circuit currents.





Products can be divided into ordinary type, anti fouling type, and plateau type according to their usage conditions
Compliant with standards: GB1984 "AC High Voltage Circuit Breakers" and IEC56 "AC High Voltage Circuit Breakers", as well as ONJ.520.023JT (Technical Conditions for Outdoor High Voltage Vacuum Circuit Breakers).
Standard product conditions:
Surrounding air temperature
Upper limit+40 ℃
The lower limit is -30 ℃ in general areas and -40 ℃ in high-altitude areas
Altitude: 2000 meters, partial pressure not exceeding 700 Pa (equivalent to a wind speed of 34 m/S), seismic intensity not exceeding 8 degrees, air pollution level III
Note: The anti pollution type is used in an environment with air pollution level IV; The high-altitude usage environment is below an altitude of 4000m.
435KV outdoor circuit breaker manufacturer 35KV outdoor column mounted intelligent watchdog with isolated vacuum circuit breakerTechnical parameters are shown in Table 1


Table 1
serial number
name
unit
data
1
rated voltage


35
2
Zui High Operating Voltage
40.5
3
Rated insulation level
1-minute power frequency withstand voltage
Dry test
95
Wet test
80
Lightning impulse withstand voltage (peak value)
185
4
rated current
A
1600
5
Rated short-circuit breaking current
KA
20/25/31.5
6
Rated breaking current of capacitor bank
A
400/630
7
Rated operating sequence
O--0.3s--CO--180s--CO
8
Rated short-circuit breaking current breaking times
time
12
9
Rated short-circuit closing current (peak)
KA
50/63/80
10
Rated peak withstand current
11
Rated short-time withstand current
20/25/31.5
12
Rated short-circuit duration
S
4
13
Total breaking time
ms
≤80
14
mechanical life
time
10000
15
Rated operating voltage
V
DC,AC:110,220
16
Rated operating current (closing)
)Open the gate
A
Electromagnetic mechanism: 147 (DC220) 294 (DC110); Spring mechanism: 5 (AC220V)
17
Allowable wear thickness of moving contact
mm
3
18
weight
kg
800
Note: High altitude type: The external insulation level is 34cm/kv. The technical data achieved after adjusting the circuit breaker is shown in Table 2