ASD320 Power Monitoring System Intelligent Control Instrument
1.1 Product Overview
ASD500The comprehensive measurement and control device for switchgear is used for3~35kVIndoor switchgear, suitable for various types of switchgear such as central cabinets, handcart cabinets, fixed cabinets, and ring main units. Equipped with a circuit simulation diagram and switch status indication, high voltage live display and phase detection, automatic temperature and humidity control, heating circuit fault alarm, opening and closing circuit integrity indication, opening and closing circuit voltage measurement, pre opening and pre closing flashing indication, wireless temperature measurement of electrical nodes, automatic human sensing lighting, voice prompts, electrical parameter measurement,RS485And EthernetCommunication interface and many other functions, integrating operation and display.
1.2Model Description

1.3 ASD320 Power Monitoring System Intelligent Control InstrumentProduct model and function
table1 ASD500Product model and function


1.4 ASD320 Power Monitoring System Intelligent Control Instrumenttechnical indicators
table2 ASD500technical indicators


1.5 ASD320 Power Monitoring System Intelligent Control InstrumentProduct Installation
ASD500The comprehensive measurement and control device of the switchgear adopts panel embedded installation. Firstly, a rectangular slot of the specified size is made on the cabinet surface. After removing the bracket, the device is embedded into the slot and then fixed with the bracket.
1.5.1Installation method

image1.2 ASD500Installation method
1.5.2Hole size (unit: millimeters)

image1.3 ASD500cutout size
1.6Wiring method
1.6.1terminal block

image1.4 ASD500Rear terminal diagram
Diagnosis, analysis and troubleshooting methods for common faults of intelligent control instruments in 2ASD320 power monitoring system
2.1 Auxiliary power failure
Does the screen not light up after the device is connected to the auxiliary power supply?
Possible cause: Incorrect sequence of external terminal wires.
Solution: Pull out the "temperature and humidity" sectionI”Temperature and humidityII”Re power on the device to determine.
2.2 Environmental temperature and humidity display malfunction
The ambient temperature and humidity values are not displayed or shown in the temperature and humidity menu“rupt”?
Possible reasons: The temperature and humidity control word is not activated or the temperature and humidity module is not properly connected.
Processing method:
1)When there is no display: "Parameters->The 'Fixed Value' menu will display 'Temperature and Humidity'1Return "or" Warm and Wet2Return "or" Warm and Wet3Set "investment return" as investment.
2)Display“rupt”Time: Check the temperature and humidityI”Temperature and humidityII”Is the temperature and humidity module connected correctly at the interface?
2.3 Alarm relay action fault
Under voltage, over-voltage, over-current, environmental temperature exceeding the limit, wireless node temperature exceeding the set limit and alarm relay not functioning?
Possible reason: The corresponding control word has not been input.
Processing method: "Parameters->The 'Fixed Value' menu sets the corresponding control word to 'Input'.
2.4 Simulation status indicator light malfunction once
Does the switch input not correspond to the status indicator light or does the status indicator light not light up?
Possible reason: The status indicator light is set incorrectly.
Processing method: "Parameters->Set the switch value corresponding to the status indicator light, and if it needs to be constantly on, set it to“ON”The unused settings are“OFF”.
2.5 通信故障
Is there a communication error between the upper computer or backend software and the device?
Possible cause: Incorrect device address or serial port parameter settings.
Processing method: "Parameters->Set the correct device address or serial port parameters for communication.
2.6 Node temperature value display fault
ASDIs there no temperature value displayed in the "Temperature Control" menu of the main body, or is there no temperature value displayed in any particular channel?
Possible reasons: The battery switch is not turned on or the sensor is not paired.
Processing method:
1)Check if the battery switch of the wireless temperature sensor is turned to“ON”End? (Battery switch from)OFFEnd dial toONAfter the end, the green light on the wireless temperature sensor flashes on and off2This indicates that the switch is turned on normally, otherwise it will be repeatedly turned on.
2)ViewASDIs the barcode on the main body consistent with the barcode on the wireless temperature sensor? If not, find the corresponding wireless temperature sensor and replace or re pair it (see this manual for details)2.2.6Under the chapter“ASDThe pairing and calibration of the main body and wireless temperature sensor "section.
ASD320 Power Monitoring System Intelligent Control Instrument