Air leakage detector/air duct airtightness tester

NegotiableUpdate on 05/22
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Air leakage detector/duct airtightness tester Pipeline air leakage detector Pipeline sealing tester is mainly used for testing the sealing of air conditioning pipelines. It can detect segmented pipelines and the installed main pipeline of the entire system to ensure the efficiency of the air conditioning system and avoid energy waste. This instrument performs testing according to relevant identification standards and can directly determine whether the sealing of the pipeline is qualified. Using touch screen operation, LCD color screen display, and a good human-machine interface for convenient user operation.
Product Details

Product Introduction

ATA-600HDuct air leakage tester, duct air leakage detector, and duct sealing tester are mainly used for testing the sealing of air conditioning ducts. They can inspect segmented ducts and the installed main duct of the entire system to ensure the efficiency of the air conditioning system and avoid energy waste. This instrument performs testing according to relevant identification standards and can directly determine whether the sealing of the pipeline is qualified. Using touch screen operation, LCD color screen display, and a good human-machine interface for convenient user operation.

Product Features:

1. Can detect the sealing performance of pipelines under positive and negative pressure

2. According to the standards:GB50243-2016 Code for Construction and Acceptance of Ventilation and Air Conditioning EngineeringEN1507:2006, EN12237:2002, Eurovent 2/2, DW/143, SMACNA Standard

3. Wide air volume measurement range, two measuring tools ensure measurement accuracy

4. The appraisal results can directly determine whether the pipeline sealing is qualified

5. Real time display of leakage volume, test pressure, temperature, and atmospheric pressure

6. Storage, browsing, and deletion of 2000 sets of data

7. 5.5-inch LCD touch screen, easy to operate

8. Simple structure and easy installation


In the figure, row EAF-RF-01: If the design static pressure is 620pa, the compressed air pressure is 1.2 times the design pressure (620x1.2=744pa). At this point

Air leakage meterFirst, pressurize to 744pa. At this point, if the air leakage value is ≤ 207.86m ³/h, it is considered qualified. If the air leakage is too large, it is necessary to check the joint points of the air duct.

Main specifications:



Model number

ATA- 600H

traffic

Fan enclose

Leakage rate:3 820 m3/h

(Customizable in large quantities up to 2000)m3/h

essence degree

Reading of±2.5%±0.1 m3/h

resolution

0.01 m3/h

static pressure

Fan enclose

± 2500 Pa

essence degree

Reading of1% ± 1Pa

resolution

0.1 Pa

temperature

Fan enclose

060

essence degree

±0.5

resolution

0.1

absolute pressure

Fan enclose

70130 kPa

essence degree

Reading of±2%

resolution

0.1kPa

electricity source

ATA-600HE

110-120V, 1 Phase50/60Hz,16A

ATA-600H

220-240V, 1 Phase50/60Hz,10A

heavy quantity

Net weight approximately50kg

ruler inch

54*50*120cm

save store

2000group