Building B, Shahe Youth Entrepreneurship Building, Changping District, Beijing
Single machine operation has high overload capacity and short-circuit protection characteristics
Overload capacity of 200% single-phase for 30 seconds
Inverter anti short circuit capability single-phase 290% for up to 5 minutes
Simultaneously possessing excellent ability to handle three-phase unbalanced loads, with a phase shift of ± 1 º at 100% unbalanced load
Strong non-linear load capacity, with output voltage distortion within 3%. The neutral rated value is designed to be 1.5 times the phase current to prevent thermal effects caused by harmonic currents.
Hipulse1+1 dual machine parallel operation adopts direct intelligent parallel current sharing technology to increase redundancy and reliability.
| capacity | 80kva | 120square | 160square | 200kva | 300square | 400square | 500kva | 600square | 800square |
| rated power | 64 kw | 96 kw | 128 kw | 160 kw | 240 kw | 320 kw | 400 kw | 480 kw | 640 kw |
| Power factor (output) | 0.8 | ||||||||
| rectifier | 6/12 pulse | 12 pulses | |||||||
| Input characteristics | |||||||||
| Rated voltage | 380400 or 415VAC, 3-phase+neutral | ||||||||
| Allowable range of variation in mains voltage | ± 15%, adjustable to ± 25% | ||||||||
| power factor | 0.95 lag (when selecting input filter) | ||||||||
| frequency | 47.5Hz~62.5Hz | ||||||||
| Current Time Varying Degree (THD) | When operating at full load with input filter, it is 9%, and when using a 12 pulse rectifier and input filter at full load, it is 4.5% | ||||||||
| Input second-order current limiting | Maximum 125% nominal input current | ||||||||
| Power 'climbing' | 20% to 100% load adjustable for 1-2 seconds | ||||||||
| Output and bypass characteristics | |||||||||
| Nominal Output Voltage | 380V/400/415V, 3-phase 3-wire system or 3-phase 4-wire system | ||||||||
| Adjustable range of output voltage | ±10% | ||||||||
| overload capacity | Three phase 125% rated load -10 minutes, 150% rated load -1 minute, single-phase 200% rated load -30 seconds | ||||||||
| Inverter short-circuit current limiting capability | Three phase 150%, 5 seconds, single-phase 290%, 5 seconds | ||||||||
| Large capacity static bypass configuration | 1000% bypass power can carry 100ms | ||||||||
| frequency | 50Hz, Can provide 60Hz according to user needs | ||||||||
| Tracking range of urban power supply | ± 1Hz, ± 2Hz (adjustable) | ||||||||
| Stability of internal clock | ± 0.1% internal clock amplitude 50Hz ± 0.01Hz | ||||||||
| System efficiency (full load) | >93%, 97% (ECOMIDE) power-saving mode | ||||||||
| Frequency tracking rate | Adjustable from 0.1Hz to 2Hz/second | ||||||||
| voltage stability | |||||||||
| steady state | ±1% | ||||||||
| transient | ± 5% (0-100% step load) | ||||||||
| Steady state response time | Restore to ± 1% steady-state output voltage within 20 milliseconds | ||||||||
| Phase transferability | |||||||||
| When carrying balanced load | 120±1 | ||||||||
| When carrying 100% unbalanced load | 120±1 | ||||||||
| Phase voltage symmetry | |||||||||
| When carrying balanced load | ±1% | ||||||||
| When carrying 100% unbalanced load | ±2% | ||||||||
| Total harmonic content (T.H.D) (with 100% load) | |||||||||
| Linear load | 1% typical value, maximum 3% | ||||||||
| With a 3:1 peak factor load | <5% | ||||||||
| Characteristics of DC power supply | |||||||||
| Number of battery cells | 192, 198, 204 units, 2V/unit | ||||||||
| Ripple component of DC power supply | <5% | ||||||||
| working environment | |||||||||
| Operating temperature range | 0 ℃ to 40 ℃ | ||||||||
| Storage temperature | -25C to 70C | ||||||||
| Continuous operating temperature | Up to 40C, 8 hours | ||||||||
| relative temperature | 0-90%, no condensation | ||||||||
| Maximum operating altitude | 1000 meters (without reducing the rated value) | ||||||||
| noise | 63db-68db | ||||||||
| protection level | Including when the door is open, the structure also complies with IP20 | ||||||||
| improve air circulation | Utilize internal intelligent fans for forced air cooling | ||||||||
| meet the standard | ISO9001 Design and Production Standard |
||||||||