Product Description: How to Translate
This product can be widely used in electronic computers, precision machine tools, CNC, computed tomography (CT), precision instruments, experimental devices, elevators, imported equipment, and AC stabilized power supplies for production lines in industrial and mining enterprises, oil fields, postal and telecommunications, textiles, railways, construction sites, schools, hospitals, hotels, national defense, scientific research and other departments. It is also suitable for low-voltage distribution end-users with low power supply voltage and large fluctuation amplitude, as well as electrical equipment with large load changes, such as elevators, cranes, mixers, and other places that require stable voltage.
Standard: JB/T 7620
Product Features:
It consists of main components such as column type contact voltage regulator, sampling, protection, control circuit, low-speed synchronous motor mechanism, compensation transformer, etc. When the voltage of the mains is unstable or fluctuates due to changes in user load, the sampling circuit processes the voltage signal and sends it to the synchronous motor, which drives the carbon brush of the column contact voltage regulator to move up and down, ensuring the stability of the output voltage. It has large capacity, low loss, high efficiency, wide voltage regulation range, high accuracy, strong protection function, and reliable operation. And it is equipped with phase loss, overvoltage, undervoltage, and overcurrent protection functions.
Technical Specifications:
Model SBW
KVA = 10 = 65374;2500
Output voltage stabilization accuracy V 380 ± 2%
Under voltage protection: If the output of V is lower than the rated voltage by -15%, the output power will be cut off after a delay of 3-5 seconds
Overvoltage protection: If the output of V exceeds the rated voltage by+10%, the output power will be cut off after a delay of 3-5 seconds
When the load device is short circuited, cut off the output power supply
When the load device experiences overcurrent, the output current is cut off
Reverse phase cut off output power supply
Cut off the output power supply due to phase loss
When the voltage regulator malfunctions or is under maintenance, the bypass is equipped with a manual or automatic power supply through device
Input voltage range V 304~456 Wide voltage Special customization
Voltage regulation speed s ≤ 0.05s (when the input voltage changes by 10%)
Temperature rise K < 60
Frequency Hz 50/60
Insulation resistance M Ω≥ 5
Voltage withstand V/1min 2000