Product Introduction
The SDP-P (D)/2L series high-power and special-purpose signal lightning arrester is designed according to the IEC communication surge protector standard and is suitable for lightning protection of signal equipment such as communication dedicated lines, telemetry signals, and remote control signals. The interface form of the product is a standard screw fixed card interface, which can protect 1-2 lines.The SDP-P/2L series has a nominal discharge current of 5kA and a rated load current of 5A, which can fully protect equipment using the latest semiconductor devices. The SDP-D/2L series has a nominal discharge current of 5kA and a rated load current of 10A, suitable for surge protection at the output end of broadcasting systems/background music amplifiers.
Performance parameters:
| model | SDP-P06V/2L | SDP-P12V/2L | SDP-P24V/2L | SDP-P24VAC/2L | SDP-P48V/2L | SDP-D120V/2L | SDP-D200V/2L |
| SPD port | Two ports | Two ports | Two ports | Two ports | Two ports | Two ports | Two ports |
| SPD category | Combination type | Combination type | Combination type | Combination type | Combination type | Combination type | Combination type |
| Rated working voltage | 6VDC | 12VDC | 24VDC | 24VAC | 48VDC | 120VAC | 200VAC |
| Maximum continuous operating voltage Uc | 7.2VDC | 15VDC | 30VDC | 30VAC | 52VDC | 150VAC | 230VAC |
| insulation resistance | ≥0.1MΩ |
≥2MΩ | ≥2MΩ | ≥2MΩ | ≥2MΩ | ≥2MΩ | ≥2MΩ |
|
Voltage protection level (1.2/50 μ s) Up line - line Line ground |
≤20V | ≤45V | ≤50V | ≤90V | ≤90V | ≤200V | ≤300V |
| ≤90V | ≤90V | ≤90V | ≤90V | ≤90V | ≤200V | ≤300V | |
| Nominal discharge current (8/20 μ s) In | 5kA, 10 times |
5kA, 10 times |
5kA, 10 times |
5kA, 10 times |
5kA, 10 times |
5kA, 10 times |
5kA, 10 times |
| Maximum discharge current (8/20 μ s) Imax | 10kA, 2 times |
10kA, 2 times |
10kA, 2 times |
10kA, 2 times |
10kA, 2 times |
10kA, 2 times |
10kA, 2 times |
| rated current | 5A |
5A |
5A |
5A |
5A |
5A |
5A |
| Communication tolerance | 5A,1s, 5 times | 5A,1s, 5 times | 5A,1s, 5 times | 5A,1s, 5 times | 5A,1s, 5 times | 5A,1s, 5 times | 5A,1s, 5 times |
| Impact tolerance capability | 1.5kV, 10/700 μ s, 10 times | ||||||
| 37.5A, 5/300 μ s 10 times | |||||||
| overstressed fault mode |
Mode 2 |
||||||
| Interface type | Screw type terminal block | ||||||
| response time | ≤1ns | ||||||
| Connecting wires | 1-2.5mm2 | ||||||
| size | Refer to the product appearance diagram | ||||||
| Shell material/shell protection level | UL94V-0/IP20 | ||||||
| Installation method | 35mm standard guide rail | ||||||
| failure mechanism | Communication line short circuited or disconnected to ground | ||||||
| Terms of Use | Atmospheric pressure: 80kPa~160kPa | ||||||
| Temperature: -40 ℃~+70 ℃ | |||||||
| Relative humidity: 5%~96% | |||||||
Scope of application:
Security system: telemetry line, remote control line, communication line
Industrial control systems: telemetry lines, remote control lines, communication lines
Lightning protection for low-power DC power supply linesBroadcasting system/background music system (SC-D only), other control systems with high signal currents
Appearance dimensions: