Welcome Customer !

Membership

Help

Shanghai Kaiyuan Automation Technology Co., Ltd
Custom manufacturer

Main Products:

cep-online>Products

Shanghai Kaiyuan Automation Technology Co., Ltd

  • E-mail

    3007052287@qq.com

  • Phone

    13482468385

  • Address

    Building 1, No. 188 Xinghuo Road, Qingcun Town, Fengxian District, Shanghai

Contact Now

Bus coupler IL PN BK-PAC

NegotiableUpdate on 03/04
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Bus coupler IL PN BK-PAC $r $nIL PN BK-PAC - Bus coupler $r $n2403696 $r $nInline, bus coupler, PROFINET, RJ45 female connector, local bus transmission rate: 500 kBit/s/2 MBit/s, protection level: IP20
Product Details

Bus coupler IL PN BK-PAC
IL PN BK-PAC
-bus coupler
2403696

Inline, Bus coupler, PROFINET, RJ45 female connector, local bus transmission rate: 500 kBit/s/2 MBit/s, protection level: IP20

总线耦合器IL PN BK-PAC总线耦合器IL PN BK-PAC总线耦合器IL PN BK-PAC

Bus coupler IL PN BK-PAC
Product Details


Bus couplers are suitable for PROFINET networks. Create connections to the Inline I/O system and the industrial I/O signals connected to it through a bus coupler. This bus coupler can connect up to 63 Inline devices. The equipment description of Phoenix Contact controllers is included in the engineering design tools PC Worx and PLCnext Engineer. Provide supporting GSDML files for integrating Inline sites into other programming systems.



Size chart
width 40 mm
height 119.4 mm
depth 71.5 mm
Notes on Dimensional Data housing dimensions

PROFINET
number of interfaces 2
connection method RJ45 female connector
Precautions for Connection Methods Adaptive and self crossover
transmission speed 100 Mbps (compliant with PROFINET standards)
Principles of Transmission Ethernet RJ45 twisted pair cable
Inline local bus
number of interfaces 1
connection method Inline data bridging block
transmission speed 500 kBit/s/2 MBit/s (automatic detection, no system combination)

System limitations
Number of supported devices 63 (per station)
The number of devices that can be connected to the local bus 63
Number of devices with parameter channels 16
Number of branch terminals supported with remote bus branches 3
PROFINET
Device Function PROFINET devices
specification Version 2.3
Update rate Minimum 1 ms (depending on the size of the bus system)
Device ID 0140hex
Vendor ID 00B0hex
module
Hexadecimal ID encoding none
Register length 16 bits

Product Type I/O components
Product Series Inline
type module
Installation location arbitrary
Number of channels 12
Insulation characteristics
Overvoltage category II (IEC 60664-1,EN 60664-1)
pollution level 2 (IEC 60664-1,EN 60664-1)

Power consumption under rated conditions 2.2 W
Potential: Bus coupler power supply UBKCommunication power supply UL(7.5 V) and analog power supply UANA(24V) Powered by a bus coupler power supply.
power supply voltage 24 V DC (via Inline connector)
Power supply voltage range 19.2 V DC... 30 V DC (including all tolerances, including ripple)
current consumption 0.91 A DC (connected to a number of I/O modules)
Typical value of 85 mA (not connected to fieldbus devices)
Potential: Communication power supply (U)L)
power supply voltage 7.5 V DC
Potential: power supply for analog module (U)ANA)
power supply voltage 24 V DC
Power supply voltage range 19.2 V DC... 30 V DC (including all tolerances, including ripple)
Potential: Main circuit (U)M)Power supply
power supply voltage 24 V DC (via Inline connector)
Power supply voltage range 19.2 V DC... 30 V DC (including all tolerances, including ripple)
Potential: segmented circuit power supply (US)
power supply voltage 24 V DC (via Inline connector)
Power supply voltage range 19.2 V DC... 30 V DC (including all tolerances, including ripple)
Electrical isolation/voltage range isolation
Test voltage resistance: Ethernet interface 1/Ethernet interface 2 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Ethernet interface 1/logic (U)BK、UL、UANA) 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Ethernet interface 1/I/O (U)M、US) 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Ethernet interface 1/functional grounding 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Ethernet interface 2/logic (U)BK、UL、UANA) 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Ethernet interface 2/I/O (U)M、US) 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Ethernet interface 2/functional grounding 1500 V AC, 50 Hz, 1 min.
Test voltage resistance: Logic (U)BK、UL、UANA)/I/O (UM、US) 500 V AC, 50 Hz, 1 min.
Test voltage resistance: Logic (U)BK、UL、UANA)/Functional grounding 500 V AC, 50 Hz, 1 min.
Test voltage resistance: I/O (U)M、US)/Functional grounding 500 V AC, 50 Hz, 1 min.

Connection technology
Connection Name Inline connector
Wire connection
connection method Pull back spring connection
Rigid wire cross-section 0.08 mm² . .. 1.5 mm²
Cross section of flexible wire 0.08 mm² . .. 1.5 mm²
Connectable guide cross-section AWG 28 . .. 16
Stripping length 8 mm
Inline connector
connection method Pull back spring connection
Cross section of hard wire 0.08 mm² . .. 1.5 mm²
Cross section of flexible wire 0.08 mm² . .. 1.5 mm²
Connectable guide cross-section AWG 28 . .. 16
Stripping length 8 mm

environmental conditions
Environmental temperature (operating) -25 °C . .. 55 °C
protection level IP20
Air pressure (operation) 70 kPa... 106 kPa (up to an altitude of 3000 meters)
Air pressure (storage/transportation) 70 kPa... 106 kPa (up to an altitude of 3000 meters)
Environmental temperature (storage/transportation) -40 °C . .. 85 °C
Allow humidity (operation) 10 % . 95% (no condensation)
Allow humidity (storage/transportation) 10 % . 95% (no condensation)

protection level III (IEC 61140,EN 61140,VDE 0140-1)

Installation Type DIN rail installation
Installation location arbitrary

Order Number 2403696
packaging unit 1 pc
Minimum order quantity 1 pc
Sales key code DRI11A
Product key code DRI11A
Catalog page Page 104 (C-6-2019)
GTIN 4055626346137
Individual weight (including packaging) 168.8 g
Individual weight (excluding packaging) 168.5 g
Tariff number 8538900000
place of origin DE