1Basic Introduction to Remote Power Supply
The application modes of remote power supply are divided into two network structures: single end (local end only) and double end (local end+remote end). The DC remote power supply system consists of two parts: local equipment and remote equipment. The basic working principle of remote power supply: The backup power supply of the computer room -48V basic power supply is isolated and boosted to DC high voltage (230-410V) by the local end equipment, and then transmitted to the remote (load) equipment end through composite optical cables or dedicated cables. The remote end then transforms the DC high voltage to the standard input voltage required by the load equipment (-48V, DC260V or AC220V) to power the remote communication equipment, providing 24-hour uninterrupted and stable power supply, as well as maintenance free power supply guarantee under harsh conditions.
Performance characteristics: It has protection functions such as output overvoltage, open circuit, short circuit, leakage, lightning protection, and strong current intrusion for transmission lines; When the above faults occur in the transmission line, the local equipment will automatically protect within ≤ 50ms, stop outputting DC high voltage, and only output the line inspection voltage of ≤ 48V. During system protection, it has sound and light alarm functions, and different protection states correspond to different indicator lights, which does not affect the normal operation of other modules. After troubleshooting, the device will automatically restore output power supply after a delay of 30 seconds, without the need for manual reset operation. Equipment anti surge function. Lightning protection levels of 20KA, 30KA, and 60KA (choose according to usage conditions). The output voltage of the remote module is adjustable.
2、 Remote supply equipment and technical specifications
1. Local end
Front of 5000W remote power supply bureau end
Back of 5000W remote power supply bureau end
| Main technical indicators of the local end | ||
| name | 5000W | 3000W |
| Local output power | ≥5000W | ≥3000W |
| Single module power | 1000W | 600W |
| Power module redundancy requirements | 4+1 | |
| Local output voltage | 230V~410V, Continuing Adjust | |
| Efficiency of local end conversion | ≥ 90.5% (48V input, 380V output, 80% load) | |
| Parallel current sharing function | possess | |
| Lightning protection bureau end DC output terminal: capable of withstanding 3 shocks of 8/20us and 30KA | ||
| Work environment indicators | ||
| Local working temperature | -20℃~+55℃ | |
| Local temperature requirements | ≤93% | |
| Local atmospheric pressure | 86kpa~106kpa | |

| Remote main technical indicators | |
| name | DC-48V 800W; 1200W; 2000W; 3000W |
| DC input voltage range | DC230V~410V |
| Remote output voltage | DC50V-54V |
| Remote conversion efficiency | ≥92% |
| Remote output ripple | ≤200mV |
| Lightning Protection | Remote DC input terminal 8/20us, with 3 impacts of 10 KA amplitude |
| Work environment indicators | |
| Remote working temperature | -50℃~+65℃ |
| Remote humidity requirements | ≤95% |
| Remote atmospheric pressure | 86kpa~106kpa |
| Outdoor remote protection level | IP65 |
| Technical indicators of lightning protection unit | |
| Lightning protection level: | 30KA或40KA |
| Function: | Lightning protection, with built-in fiber optic disc and photoelectric separation |
| Overall dimensions: | Waterproof shell: (320 * 200 * 100mm) |
| Installation method: | Wall mounted and pole mounted |
| Allocation unit technical indicators | |
| Number of input channels: | 1 Road |
| Number of output channels: | Route 1, Route 5, Route 10 |
| Function: | Open circuit, overload |
| Structural dimensions: | Indoor type: 19 inches 1U high, indoor type (480 * 250 * 25mm) |
| Installation method: | Waterproof type: wall mounted, pole mounted; Indoor type: 19 inch standard cabinet |