The Honeywell FS7 photoelectric flame detector from the United States has been specially designed, and its unique secondary fire detection is not affected by false alarm sources, making it suitable for fire protection applications in semiconductor cleanrooms.

Product Details

Honeywell FS7 photoelectric flame detector produced in the United StatesProduct Introduction:

The Honeywell FS7 photoelectric flame detector from the United States has been specially designed, and its unique secondary fire detection is not affected by false alarm sources, making it suitable for fire protection applications in semiconductor cleanrooms. FS7 flame detector provides intelligent secondary response for semiconductor wet workbench fire:

Level 1: Warning. This is the first level response in the event of a small fire (producing 3 kilowatts of thermal energy, equivalent to the heat generated when a 4-foot diameter polypropylene oil tank catches fire). This response provides a certain amount of time for the flame to extinguish on its own.

Level 2: Alarm. If the flame cannot extinguish on its own and reaches the thermal energy threshold specified by Facory Mutual (i.e. 13 kilowatts, equivalent to the heat generated when an 8-inch diameter polypropylene oil tank catches fire). It will activate the second level response.


Honeywell FS7 photoelectric flame detector product features:

Multi spectral infrared flame detector

Unique bipolar flame detection response

No false positives

Not affected by smoke, gas, or chemical vapor

Not affected by thermal radiation sources such as electric heaters and ovens

Can detect both hydrocarbon and non hydrocarbon flames

Special injection molded casing, waterproof, heat-insulating, acid resistant, and corrosion-resistant

120 degree wide viewing angle

RS-485 digital interface

FirePicTM fire accident time and date record

Built in self-test function

Integrated pattern design can run independently



Technical parameters of Honeywell FS7 photoelectric flame detector product:

response time

Warning: 4 "diameter polypropylene fire (3KW) less than 5 seconds

Alarm: 8 "diameter polypropylene fire (13KW) less than 5 seconds

field of view

Vertical and horizontal 120 º field of view

spectral sensitivity

Broadband infrared light: 0.7 to 3.5um

Narrowband infrared light: 0.7 to 1.1um

Visible light: 400 to 700nm

INPUT VOLTAGE

10-12VDC of FSC controller

Power consumption

30mA@12VDC

Self inspection

Self check every 10 seconds

Output

RS485 FireBus for FSC controller or control card

operation temperature

+32 to+131 º F 0 to+55 ℃

Humidity

10 to 90% RH, no condensation

Shell

Polypropylene sealing, heat-resistant, injection molding


Protection level: IP67 dustproof and waterproof

mounting bracket

Sliding installation bracket

electrical interface

20 foot 14 wire cable with locking plug and unplug terminals to terminal box