Product Name:JJW(JSW)series Precision purification stabilized power supply
Product Category: Voltage Regulator (Purification Power Supply)
Capacity range:1KVA~100KVA
Product Introduction:JJW series precision purification communicationvoltage regulatorThe power regulation technology adopts the internationally advanced sine energy distribution program, representing the latest development level of AC voltage regulation technology. Its circuit consists of a sine energy divider and a high-power filter connected in parallel. It has high voltage stabilization accuracy, high overload capacity, good reliability, strong anti-interference ability, high efficiency, can work continuously for a long time, has a long service life, and is suitable for various types of loadsAdvantages such as resistance, sensitivity, and capacitance make it a replacement for the 614 series electronic systemvoltage regulatorMagnetic saturationvoltage regulatorThe Ideal Replacement Product
Main technical indicators and functions
serial number |
project |
Technical indicators and functions |
|
JJW series | |||
1 |
Capacity |
10KVA~100KVA |
|
2 |
input voltage |
220V ± 20% or wide voltage special customization |
|
3 |
output voltage |
Optional within 220V ± 5% |
|
4 |
voltage regulation accuracy |
1% -5% optional |
|
5 |
stabilization time |
When the input voltage undergoes a 10% step change relative to the rated value, its stabilization time is ≤ 1s |
|
6 |
guarantee protect merit can |
overvoltage |
Output voltage exceeding 5% of rated voltage, delay for 3-5 seconds to cut off output power supply |
undervoltage |
Output voltage below -13% of rated voltage, delay for 3-5 seconds to cut off output power supply |
||
short circuit |
When the load device is short circuited, cut off the output power supply |
||
overcurrent |
When the load device is overcurrent, cut off the output power supply |
||
Reverse phase |
Cut off the output power supply |
||
phase loss |
Cut off the output power supply |
||
bypass |
When the voltage regulator malfunctions or is repaired, it is equipped with a manual or automatic power supply through device |
||
7 |
frequency |
50Hz/60Hz |
|
8 |
Source voltage effect |
≤±0.5% |
|
9 |
Load effect |
≤±1% |
|
10 |
response time |
≤50ms |
|
11 |
Additional waveform distortion |
≤± 5% (additional) |
|
12 |
relative humidity |
≤90% |
|
13 |
Peak absorption |
Input 1000V/3us peak output ≤ 5V |
|
14 |
insulation resistance |
>5M euros |
|
15 |
Load power factor |
>0.9 |
|
16 |
ambient temperature |
-5~+40℃ |
|
17 |
efficiency |
||