E-mail
bwt-sh@163.com
-
Phone
13818612430
-
Address
Room 514, No. 1, Lane 775, Siping Road, Shanghai
Shanghai Pengshengda Electric Co., Ltd
bwt-sh@163.com
13818612430
Room 514, No. 1, Lane 775, Siping Road, Shanghai
Product Name: Stable Transformer Integrated Cabinet
Product Category: Stable Transformer Integrated Machine
Capacity range:5KVA~500KVA
Product Introduction:Our products are specifically designed for factoriesimported equipment Supporting the production of voltage stabilizers. We assist in developing project plans, optimizing system solutions, and participating in the technical decomposition and import of bidding projects based on the different situations and needs of our clients.SBW-SGCompensatory series three-phase AC voltage stabilizerIntegrated cabinet, Compared to other types of voltage regulators, the productAdded an isolation transformer,This product is mainly aimed at importsLarge scale electromechanical equipment, metal processing equipment, production lines, construction equipment, elevators, medical equipment, microcomputer rooms, computer control equipment, embroidery light equipmentProducts that require voltage transformation and stabilization.
Input voltage three-phase380VOutput voltage three-phase220V(or customized voltage).
Voltage stabilization followed by isolation or isolation followed by voltage stabilization can be used simultaneously.
basic indicators
Capacity |
5KVA £65374;500KVA |
Output power factor |
0.8 |
input voltage |
380V ± 15% (two-phase or three-phase) |
output voltage |
220V ± 5% (single-phase) |
voltage regulation accuracy |
Factory setting 2.5% (adjustable from 1% to 5%) |
Frequency |
50Hz/60Hz ± 2% |
protection function
Overvoltage |
Output voltage exceeding 10% of rated voltage (adjustable), with a delay of 3-5 seconds to cut off the output power supply |
Undervoltage |
Output voltage lower than 15% of rated voltage (adjustable), delay 3-5 seconds to cut off output power supply |
Short circuit |
When the load device is short circuited, cut off the output power supply |
Reverse phase |
When there is an error in the three-phase electrical phase sequence, the machine will sound an alarm and cut off the output power supply |
Lack of phase |
When there is a phase loss in three-phase electricity, the machine will sound an alarm and cut off the power supply |
Heat dissipation |
fan |
other
Additional waveform distortion |
≤ 1% |
Asymmetric degree of additional voltage |
Output to input asymmetry increment ≤ 1% |
noise |
≤ 55dB |
efficiency |
Capacity < 40KVA ≥ 94% |
Capacity 40-200KVA ≥ 98% | |
insulation class |
FGrade(otherCustomizable) |
pressure resistance |
The voltage regulator has no breakdown or arcing phenomenon at 2000VAC/min to ground |
The isolation transformer has no breakdown or arcing phenomenon at 2500VAC/min to ground | |
insulation resistance |
The whole machine has a ground resistance of ≥ 2M Ω |
Input/output cable |
Install from the front and bottom |