Temperature rise experiment power supply

NegotiableUpdate on 05/07
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Function Introduction: The temperature rise dedicated high current generator is mainly used for current load testing and temperature rise testing of bus ducts, switches, switchgear, and other electrical equipment. Main technical indicators: The current value is determined by the customer according to their needs, and the brand can output AC current ..
Product Details

Function Introduction:

The dedicated high current generator for temperature rise is mainly used for current load testing and temperature rise testing of bus ducts, switches, switchgear, and other electrical equipment.

  

Main technical indicators:The current value is determined by the customer according to their needs

brand

Nenghua

High output current

AC single-phase 8000A 3 groups

Circuit method

igbt inverter

communication input

phase line

3Φ4W +G

voltage

380V ± 10%, 50Hz ± 2% three-phase four wire

input current

834A

output

phase line

1Φ2W +G

open-circuit voltage

0-20V automatic conversion

current

AC 0-8000A continuous adjustable accuracy: 0.5

Steady current accuracy

Output current ≤± 0.2%

output terminal

terminal block

protect

Electronic circuits quickly detect overvoltage, overcurrent, and high-temperature automatic tripping protection and alarm devices. Non test state voltage is zero and current is zero

display

and

setting

Voltage meter display

Digital voltmeter resolution 0.1V

Current meter display

Digital ammeter resolution 1A

Adjust settings

Current (high precision potentiometer adjustment)

be

unify

overall efficiency

≥90%

Voltage resistant insulation impedance

AC 1800V for 1 minute, 20 megaohms

cooling system

Natural air cooling

noise

< 60dB (1mm in front of the machine)

Transformer accuracy

0.2S level

Protection level

IP20

work

environment

temperature

-10℃-50℃

humidity

0-90% (non condensing state)

altitude