E-mail
shengxudianqi@126.com
-
Phone
13621915063
-
Address
No. 14, Lane 466, Jiangyang South Road, Zhabei District, Shanghai
Shanghai Shengxu Electric Co., Ltd
shengxudianqi@126.com
13621915063
No. 14, Lane 466, Jiangyang South Road, Zhabei District, Shanghai
Product Introduction
KT6900 Intelligent Wireless High and Low Voltage Nuclear Phase AnalyzerIt consists of a detector, receiver (host), telescopic insulation rod, monitoring software, USB communication cable, etc. Its wireless transmission of test data can penetrate through wall obstacles, with a linear transmission distance of about 80 meters. The host adopts a 4.3-inch 65K color LCD screen, which can display phase, frequency, phase sequence, and nuclear phase results on the same screen, with dynamic vector diagram indication, clear and intuitive; Having voice prompts such as "X signal normal, Y signal normal, in-phase, out of phase" will make testing simple and easy; The host is also designed with a USB interface, and the data saved during on-site testing can be imported into the computer through monitoring software for easy access and management of historical data. The insulating rod is made of alkali free glass fiber cloth as the base material, and is heated, rolled, baked, and cured with epoxy phenolic resin as the adhesive. It has the characteristics of high insulation, stretchability, moisture resistance, impact resistance, bending resistance, and lightweight.
Due toKT6900 Intelligent Wireless High and Low Voltage Nuclear Phase AnalyzerSome users may not use it frequently, or even use it only once every six months. If they do not forget to charge the battery for a long time, it may cause the battery to not work properly. Users may also find it inconvenient to purchase rechargeable batteries of the same specifications. Therefore, KT6900 has designed two battery power supply methods. When the rechargeable battery is damaged, ordinary batteries can be purchased for replacement (the host uses 6 1.5V LR6 batteries); The detector uses two pieces of 6F22 9V.
Product features:
Nuclear phase, electrical verification, phase, frequency, and phase sequence testing
B fully intelligent, wireless transmission, voice core phase
C 10V~550kV voltage automatic phase detection
D 10V low voltage precise nuclear phase
Wireless transmission distance of 100m
F-20 °~20 ° in-phase; 100 ° -140 °, 220 ° -260 ° out of phase
G Self calibration error ≤± 3 °; On site in-phase error ≤± 7 °, out of phase error ≤± 12 °
H Phase resolution 1 °
The shrinkage state of the insulation rod is 600mm; the elongation state is 3200mm; the withstand voltage is ≤ 110kV
4.3-inch 65K color screen display
Voice functions such as "in-phase" and "out of phase"
USB interface, 200 sets of data storage, software monitoring, data uploading to computer
Technical Specifications:
Function: High and low voltage wireless voice core phase, phase testing, phase sequence judgment, electrical verification, frequency testing, etc
Power supply: Detector: 7V~9VDC (built-in large capacity rechargeable lithium battery, 7.4V/1000mAh, fully charged and continuously working for 40 hours)
Receiver: 7V~9VDC (LR6, 1.2V, 6 high-capacity nickel hydrogen rechargeable batteries, total 9000mAh, fully charged, continuous operation for 40 hours)
Nuclear phase method: Contact type Nuclear phase: Lines below 400V can contact the conductor Nuclear phase
Non contact core phase: For lines above 400V, the detector can be gradually hooked closer to the core phase of the wire without directly contacting the high-voltage wire. When the voltage exceeds 35kV, non-contact core phase must be used.
Transmission distance: wireless transmission, linear transmission distance of about 80m
Transmission frequency: 433MHz, 315MHz
Nuclear phase voltage: 10V~500kV
Phase differentiation: -20 ° to 20 ° in-phase; 100 ° -140 ° and 220 ° -260 ° out of phase
Accuracy: Self calibration error ≤± 3 °; On site in-phase error ≤ ± 7 °; On site out of phase error ≤ ± 12 °; Resolution 1 °
Insulation rod length: φ 28mm; Shrinkage is 600mm; elongation is 3200mm
LCD 4.3-inch; 65K color screen; Display area 98mm × 57mm
Phase indication: Both phasor diagram and numerical indication are provided, with clear and intuitive probe hook size of φ 5mm × D50mm and probe size of φ 5mm × L40mm
Voice function: with voice prompts such as "in-phase, out of phase, normal X signal, normal Y signal"
Electricity verification prompt: When there is electricity, the detector emits a "beep beep beep beep" prompt sound
Data interface: USB mini interface
Data storage: 200 sets, press the HOLD key to hold the data and automatically number it for storage, display the "FULL" symbol when the storage is full (data will not be lost during power failure or battery replacement)
Data retention: Press the HOLD key to hold the data, and the HOLD symbol will be displayed. Press the HOLD key again to cancel the retention
Data lookup: Press the READ key to enter data lookup mode, and then press the arrow keys to flip through the data
Backlight: Yes, suitable for dim places
Display rate: 3 times/second
Shifting: 10V~550kV fully automatic shifting phase
Test instruction: During testing, it displays "Under Test ---"
Automatic shutdown: After about 15 minutes of startup, the instrument panel will automatically shut down
Battery voltage: When the battery voltage is below 6.5V, the low battery voltage symbol is displayed, reminding that the battery needs to be charged or replaced.
Instrument quality host: 700g (including battery)
Detector: 200g × 2 (including battery)
Insulation rod: 430g × 2
Total weight: 6kg (including instrument box and insulation rod)
Instrument size host: length, width, thickness 195mm × 137mm × 50mm; detector: length, width, thickness 145mm × 58mm × 50mm
Instrument box dimensions: length, width, and height: 640mm × 310mm × 120mm
USB cable length: USB data cable length 1.5m
External interference without particularly strong electromagnetic fields; No co frequency interference at 433MHz and 315MHz
Working temperature and humidity range from -20 ℃ to 45 ℃; Below 80% Rh
Storage temperature and humidity -10 ℃~60 ℃; Below 70% Rh