Fiber rotary filter equipmentThe wiring terminals inside the electrical control cabinet should be checked for looseness every three months. If there is such a situation, the wiring terminals should be tightened. When there is a fault in the electrical part, the electrical circuit should be checked according to the electrical schematic to see if it is normal, if the circuit breaker trips, and if the insurance is burned out. The cause should be identified and resolved before power can be restored. Common faults and maintenance of electrical equipment in fiber rotary filter: 1Fiber rotary filter equipmentReason for motor circuit breaker tripping: (1) Loose or disconnected joints and terminals; (2) The current setting value of the circuit breaker is too small. Countermeasure: (1) Connect and fasten the terminals correctly; (2) Adjust the current setting of the circuit breaker according to the rated current of the motor.
2. Reason for tripping of water pump motor circuit breaker: (1) Loose or disconnected joint and terminal; (2) The current setting value of the circuit breaker is too small; (3) The water pump has a loud noise. Countermeasure: (1) Connect and fasten the terminals correctly; (2) Adjust the current setting of the circuit breaker according to the rated current of the motor; (3) Reverse the motor and adjust the motor phase sequence.
3. Reason for the water pump not producing water: (1) Leakage in the pipeline; (2) Motor reversal. Countermeasure: (1) Tighten the screws of the pipeline to make it sealed; (2) Adjust the motor phase sequence.
4. Electric valve motor does not start, reason: (1) not connected to power supply; (2) Disconnection, detachment of connectors from terminals; (3) The power supply voltage is incorrect or too low; (4) Overheating protector action (whether the ambient temperature is too high, whether the valve is stuck); (5) The micro opening action is not good; (6) The startup capacitor is not functioning properly. Countermeasure: (1) Connect the power supply properly; (2) Repair broken wires and correctly connect and tighten terminals; (3) Go check if the voltage is normal; (4) Reduce the ambient temperature and manually check if the valve opening and closing are normal; (5) Replace the micro switch; (6) Replace the capacitor with the manufacturer.
5. The reason why the electric valve opening and closing indicator light does not light up is: (1) the light bulb is broken; (2) The micro switch is not functioning properly. Countermeasure: (1) Replace the light bulb; (2) Replace the micro switch.
6. The reason why the motor cannot stop running when the electric valve reaches the position is: (1) poor switch action; (2) Reverse the phase sequence of three-phase AC power supply; (3) Error in connecting limit switch to control circuit; (4) Mechanical limit advance action. Countermeasure: (1) Replace the switch; (2) Adjust the three-phase AC phase sequence; (3) Adjust the wiring; (4) Adjust the mechanical limit again according to the adjustment instructions of the mechanical limit block.